Functional safety
8.1 General safety notes
SIPART PS2 with and without HART communications
102 Operating Instructions, 09/2007, A5E00074631-07
Functioning of the system as shown in the example
The transmitter generates a process-specific analog signal. The downstream control system
monitors this signal to ensure that it does not fall below or exceed a set limit value. In case of
a fault, the control system generates a failure signal of < 3.6 mA or > 22 mA for the
connected positioner, which switches the associated valve to the specified safety position.
8.1.2 Safety Integrity Level (SIL)
The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL) from
SIL 1 to SIL 4. Each level corresponds to the probability range for the failure of a safety
function.
Description
The following table shows the dependency of the SIL on the "average probability of
dangerous failures of a safety function of the entire safety-instrumented system" (PFD
AVG
)
The table deals with "Low demand mode", i.e. the safety function is required a maximum of
once per year on average.
Table 8-1 Safety Integrity Level
SIL Interval
4 10
-5
≤ PFD
AVG
< 10
-4
3 10
-4
≤ PFD
AVG
< 10
-3
2 10
-3
≤ PFD
AVG
< 10
-2
1 10
-2
≤ PFD
AVG
< 10
-1
The "average probability of dangerous failures of the entire safety-instrumented system"
(PFD
AVG
) is normally split between the three sub-systems in the following figure.
6HQVRU
HJSUHVVXUH
WHPSHUDWXUHHWF
&RQWUROV\VWHP
RUORJLFXQLW
HJ
3/&
3)'
$9*
FRPSRQHQW
)LQDOFRQWUROOLQJ
HOHPHQW
HJYDOYHZLWKDFWXDWRU
DQGSRVLWLRQHU
Figure 8-2 Example of PFD distribution