
Technical data
13.3 Technical data of optional modules
SIPART PS2 with and without HART communications
206 Operating Instructions, 09/2007, A5E00074631-07
Connections
Basic unit without
explosion protection
Basic unit with
explosion protection
EEX d (explosion-
proof housing)
Basic unit with
explosion protection
EEx ia/ib
Basic unit with
explosion protection
EEx n
• electrical
Screw terminals 2.5
AWG28-12
Cable penetration
M20x1.5 or ½-
14NPT
Screw terminals 2.5
AWG28-12
EEx d-certified cable
penetration
M20x1.5, ½-14NPT
or M25x1.5
Screw terminals 2.5
AWG28-12
Cable penetration
M20x1.5 or ½-
14NPT
Screw terminals 2.5
AWG28-12
Cable penetration
M20x1.5 or ½-
14NPT
• pneumatic
Female thread G1/4
DIN45141 or ¼-18
NPT
Female thread G1/4
DIN45141 or ¼-18
NPT
Female thread G1/4
DIN45141 or ¼-18
NPT
Female thread G1/4
DIN45141 or ¼-18
NPT
External position sensor
(potentiometer or NCS,
optional)
• V
o
- - < 5 V < 5 V
• I
o
- - < 75 mA < 75 mA
• I
s
- - < 160 mA < 160 mA
• P
o
- - < 120 mW < 120 mW
highest permitted external
capacity C
o
- - < 1 μF < 1 μF
highest permitted external
inductance L
o
- - < 1 mH < 1 mH
13.3 Technical data of optional modules
Optional modules
Without explosion
protection
(also EEx d)
With EEx ia/ib explosion
protection
With EEx n explosion
protection
Explosion protection as per
EN 50014 and EN 50020 and
EN 50021
- II 2G EEx ia/ib II C
T4/T5/T6
1
)
II 3G EEx nA L [L] II C T6
Installation point - Zone 1 Zone 2
Permissible ambient temperature for
operation
(For devices with explosion
protection: only in combination with
the 6DR5***-*?E*** standard
controller; only T4 is permitted for
use with the I
y
module.)
-30 ... +80°C
(-22 ... +176°F)
T4: -30 ... +80°C (-22 ... +176°F)
1)
T5: -30 ... +65°C (-22 ... +149°F)
1)
T6: -30 ... +50°C (-22 ... +122°F)
1)
1)
only in combination with the 6DR5***-*E*** standard controller; only T4 is permitted for use with the I
y
module.
Comentarios a estos manuales