Parameterizing/addressing
10.4 Description of parameters
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
153
In advanced diagnosis, the threshold of the fault message is displayed using columns in
addition to the error code. These columns are shown on the digital display as follows:
Figure 10-6 Display of a threshold 1 error message
Figure 10-7 Display of a threshold 2 error message
Figure 10-8 Display of a threshold 3 error message
The factory setting is "OFF".
10.4.3 Description of parameters A through P
10.4.3.1 Description of parameter A
A.
PST - partial stroke test
Use this parameter to activate the partial stroke test for cyclic or manual test of up/down and
servo solenoid valves. Set the "On" parameter value to activate the test. Sub-parameters are
displayed. If the sub-parameters are set to the desired parameter values, initiate the partial
stroke test using:
● Buttons on the device
● A binary input
● Communication
● A cyclic test interval
Sub-parameters are described below.
The factory setting is "OFF".