Alarm, error, and system messages
11.1 Representation of system messages in the digital display
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
175
Line
ok x The permissible measuring range of end
positions is achieved only in case of a
manual initialization
Acknowledge with the operating mode
button; the remaining steps ("RUN1" to
"FINSH") execute automatically
RUN1 /
ERROR
X Error in "RUN1", no movement e.g. due to
the lack of compressed air
Provide adequate compressed air
Open the restrictor(s)
Restart the initialization process
d___U X Bar graph display of the zero point; zero
point is beyond the tolerance range
Set between "P 4.0" and "P .9" ( >0< )
using a friction clutch
Continue with the "+" or "-" button
SEt X
MIDDL X
Friction clutch was moved; "P 50.0" not
displayed when the lever is horizontal
In case of linear actuators, use the "+"
and "-" buttons to bring the lever
perpendicular to the spindle
Press the operating mode button slightly
to acknowledge (the initialization process
is continued)
UP > X "UP" tolerance range was exceeded or the
inactive zone of the potentiometer was
covered
Increase the effective lever length of the
linear actuators or switch the
transmission ratio selector to 90°
Press the operating mode button slightly
to acknowledge
Restart the initialization process
90_95 X Possible only in case of part-turn actuators:
actuator travel is not in the range between 90
and 95%
Use the "+" and "-" buttons to move it in
the range between 90 and 95%
Press the operating mode button slightly
to acknowledge
U-d> X "Up-Down" measuring span was undershot
Decrease the effective lever length of the
linear actuators or switch the
transmission ratio selector to 33°
Press the operating mode button slightly
to acknowledge
Restart the initialization process
U nn.n X
D->U X
Display of the "Up" actuating time
Wait, or
To change the actuating time, interrupt
the initialization process with the "-"
button, or
Activate the leakage test with the "+"
button
D nn.n X
U->d X
Display of the "Down" actuating time
Wait, or
To change the actuating time, interrupt
the initialization process with the "-"
button, or
Activate the leakage test with the "+"
button
NOZZL X Actuator stops (the initialization process was
interrupted using the "-" button when the
actuation speed display was active)
The actuating time can be changed by
adjusting the restrictor(s)
Redetermine the speed of shifting using
the "-" button
Continue with the "+" button
TESt X
LEAKG X
Leakage test active (the "+" button was
pressed when the actuation speed display
was active)
Wait for 1 minute
Continue with the "+" button