Alarm, error, and system messages
11.2 Diagnosis
SIPART PS2 with and without HART communications
180 Operating Instructions, 09/2007, A5E00074631-07
No. Abbreviation Meaning Values that can
be displayed
Unit Reset
possibl
e
28 TEMP Current temperature -40 ... 85 °C -
29 TMIN Minimum temperature ("min/max pointer") -40 ... 85 °C -
30 TMAX Maximum temperature ("min/max pointer") -40 ... 85 °C -
31 T1 Number of operating hours in temperature range 1 0 ... 4.29E9 Hours -
32 T2 Number of operating hours in temperature range 2 0 ... 4.29E9 Hours -
33 T3 Number of operating hours in temperature range 3 0 ... 4.29E9 Hours -
34 T4 Number of operating hours in temperature range 4 0 ... 4.29E9 Hours -
35 T5 Number of operating hours in temperature range 5 0 ... 4.29E9 Hours -
36 T6 Number of operating hours in temperature range 6 0 ... 4.29E9 Hours -
37 T7 Number of operating hours in temperature range 7 0 ... 4.29E9 Hours -
38 T8 Number of operating hours in temperature range 8 0 ... 4.29E9 Hours -
39 T9 Number of operating hours in temperature range 9 0 ... 4.29E9 Hours -
40 VENT1 Number of switching cycles of pilot valve 1 0 ... 4.29E9 - -
41 VENT2 Number of switching cycles of pilot valve 2 0 ... 4.29E9 - -
42 STORE Save the current value as "last maintenance" (press
the increment button for 5 s) (Store)
- - -
43 PRUP Prediction up 1 ... 40 - -
44 PRDN Prediction down 1 ... 40 - -
45 WT00 Number of operating hours in the actuating range
WT00
0 ... 4.29E9 Hours X
46 WT05 Number of operating hours in the actuating range
WT05
0 ... 4.29E9 Hours X
47 WT10 Number of operating hours in the actuating range
WT10
0 ... 4.29E9 Hours X
48 WT30 Number of operating hours in the actuating range
WT30
0 ... 4.29E9 Hours X
49 WT50 Number of operating hours in the actuating range
WT50
0 ... 4.29E9 Hours X
50 WT70 Number of operating hours in the actuating range
WT70
0 ... 4.29E9 Hours X
51 WT90 Number of operating hours in the actuating range
WT90
0 ... 4.29E9 Hours X
52 WT95 Number of operating hours in the actuating range
WT95
0 ... 4.29E9 Hours X
Diagnostic value 53
No. Abbreviation Meaning Values that can
be displayed
Unit Reset
possibl
e
53 mA Setpoint current 0.0 to 20.0 mA --