Mounting
4.7 External position displacement sensor
SIPART PS2 with and without HART communications
48 Operating Instructions, 09/2007, A5E00074631-07
4.7 External position displacement sensor
WARNING
Versions with flameproof enclosures may not be operated with an external position
detection system.
The aforementioned measures are not adequate in some applications. For example,
continuous and strong vibrations, high or too low ambient temperatures and nuclear
radiation.
The position displacement sensor and the control unit are mounted separately for these
applications. A universal component is available for this purpose. It is suitable for part-turn
and linear actuators. You will require the following:
An external position detection system with the order number C73451-A430-D78
comprising a positioner enclosure with an integrated friction clutch, potentiometer as well
as different blanking plugs and seals.
Or a contactless explosion-proof non-contacting position Sensor (e.g.6DR4004-6N).
A positioner
A three-pole cable to connect components.
An EMC filter module with the order number C73451-A430–D23 is provided in a set along
with cable clamps and M20 cable glands.
The EMC filter module is always used for the control unit whenever an external position
sensor is used instead of the external position detection system. An external position sensor
is, e.g. a potentiometer with a 10 kΩ resistance or a non-contacting position sensor.