Commissioning
9.2 Commissioning linear actuators
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
119
6. Start the initialization process. To do this, press the increment button for at least 5
seconds until the digital display shows the following:
7. The current potentiometer position is shown on the digital display after 5 seconds.
Examples of the displayed potentiometer positions are given below:
8. Determine the end position 1 of the actuator spindle. Move the actuator spindle to the
desired position by pressing the
increment or decrement buttons. Accept the
current position of the actuator spindle by pressing the
operating mode button. The
following is shown on the digital display:
Note
"RANGE" fault message
The selected end position is beyond the permissible measuring range if the "RANGE"
message appears on the digital display. Correct the settings as follows:
Move the friction clutch until the digital display shows "OK". Press the
operating
mode button again.
Move the actuator spindle to another position using the
increment or decrement
buttons.
Abort the manual initialization process by pressing the
operating mode button.
Switch to the "P manual mode" and adjust the actuator travel and the position
displacement sensor.
9. Determine the end position 2 of the actuator spindle. Move the actuator spindle to the
desired position by pressing the
increment or decrement buttons. Accept the
current position of the actuator spindle by pressing the
operating mode button.
Note
"Set Middl" fault message
The lever arm is not in the horizontal position if the "Set Middl" message appears on the
digital display. To correct the fault, set the reference point of the sine correction. Proceed
as follows:
1. Move the lever arm to the horizontal position by pressing the
increment or
decrement buttons.
2. Press the
operating mode button.
10. The initialization process is automatically resumed. Displays for the initialization steps
from "RUN1" to "RUN5" are shown in the lower line on the digital display.