Parameterizing/addressing
10.4 Description of parameters
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
141
Note
If the positioner has already been initialized and if the "INITA" and "INITM" values are set, it
is possible to reset the positioner to the non-initialized status. For this purpose, press the
decrement button for at least five seconds.
The factory setting is "NOINI".
See also
Commissioning (Page 107)
Sequence of automatic initialization (Page 108)
Manual initialization of linear actuators (Page 117)
Manual initialization of part-turn actuators (Page 123)
10.4.2 Description of parameters 6 through 51
10.4.2.1 Description of parameters 6
6.SCUR - Current range of setpoint
This parameter is used to set the current range of the setpoint. The selection of the current
range depends on the type of connection. Parameter value "0 MA" (0 to 20 mA) is only
possible for three-wire and four-wire connections.
The factory setting is "4 MA".
See also
Basic device (Page 70)
Description of parameters 7 (Page 141)
10.4.2.2 Description of parameters 7
7.SDIR - Setpoint direction
This parameter is used to set the setpoint direction. The setpoint direction is used to reverse
the direction of action of the setpoint. The setpoint direction is primarily used for single-acting
actuators with the safety setting "up".
See figure in
Description of parameters 7 (Page 141).
The factory setting is "riSE".