Alarm, error, and system messages
11.1 Representation of system messages in the digital display
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
177
Messages during operation:
Line Mode Message
Abov
e
Below Automatic Manual P-manual
Meaning / cause Measure
CPUSTA
RT
X
X
Message after application
of electrical auxiliary
power
Maintenance
HW /
ERROR
X Fault in the hardware
Replace
electronics
NOINI X X Positioner is not initialized
Start initialization
nnn.n X X X Actual position [in %] for
initialized positioner.
Flashing decimal point
shows communication
with a class-2 master
AUTnn X X Automatic mode (nn =
setpoint)
MANnn X Manual mode
(nn = setpoint)
Switch to
automatic mode
with mode button
oFL /
127.9
X X X Display range exceeded.
Possible causes:
Friction clutch or
transmission ratio
selector was disturbed
or
Positioner was
installed on a different
actuator without being
reinitialized
Offset friction
clutch so that
when the actuator
moves the actual
value display
stays between 0.0
and 100.0, or
transmission ratio
selector, or
perform factory
settings (Preset)
and initialization
EXSTP X X Actuator was stopped with
the binary input
EX UP X X Actuator is moved to the
upper stop with binary
input
EXDWN X X Actuator is moved to the
lower stop with binary
input
EXTPSt Partial-Stroke-Test was
activated, e.g. through
binary input
InPSt Cyclic
Partial-Stroke-Test
HTCNF X X X X HART configuration
running