Alarm, error, and system messages
11.3 Online diagnostics
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
191
at the time of initialization. The activation of "down tight closing" ("YCLS" parameter) is
therefore the condition.
Example: A value of 3% is set. The position is normally adopted for "down tight closing". A
fault is reported if a value > 3% or < -3% is determined instead.
The fault message remains activated until either a subsequent monitoring remains within the
tolerance or a re-initialization process is executed. Even the deactivation of monitoring
("F.
ZERO"=OFF) may trigger a fault message.
This monitoring function does not deliver any utilizable results if the end stops were not
determined automatically at the time of initialization, but the limits were set manually (manual
initialization, "5.INITM").
A similar diagnostics is carried out for the upper hard end stop. The "G.
OPEN" parameter is
used to set the limit for this. The activation of "up tight closing" ("YCLS" parameter) is
therefore the condition.
8 Monitoring of dead zone adjustment
If the dead zone increases disproportionately when adjusting it automatically ("DEBA"=Auto
parameter), it indicates an error in the system (e.g. severely increased packing gland friction,
play in the position displacement sensor, leakage). A limit can therefore be entered for this
value ("E1.LEVL3", threshold for dead zone monitoring). A fault message output is activated
when this value is exceeded.
9 Partial stroke test exceeds the reference step time
On the one hand, this fault message appears when a manual or cyclic partial stroke test is
initiated and the test cannot be started since the valve is not within the start tolerance. On
the other hand, this fault message appears when one of the three thresholds of the partial
stroke test that are determined from the "A6.PSTIN" reference step time multiplied by factors
"A7.FACT1" to "A9.FACT3" is violated. The degree of the fault message is shown in the
number of columns on the digital display. The degree of the fault message is simultaneously
displayed using the fault message output or alarm outputs depending on the mode of the
advanced diagnostics.
10 General control valve fault
The monitoring of the operational response responds when the actual valve position shifts
from a narrow corridor between the reference variable and the expected position course. In
this case, the deviation between the expected and actual position course is filtered,
displayed and compared with the set thresholds that are determined from the "b2.LIMIT" limit
multiplied by the factors "b3.FACT1" to "b5.FACT3".
11 Pneumatic leakage
This fault message appears when the leakage indicator exceeds the set thresholds. Keep in
mind that the complete sensitivity of this function can be used only if a ramp movement was
initiated after initialization to set the leakage indicator (see explanations for "C1.LIMIT").