Connection
6.2 Pneumatic connection
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
89
6.2 Pneumatic connection
WARNING
Owing to safety reasons, the pneumatic auxiliary power supply must be fed after installation
only if the positioner is switched to the "P-manual mode" when an electrical signal is
available, refer to the as-delivered condition.
NOTICE
Observe the specifications regarding the air quality.
If required, connect the pressure gauge block for supply air and actuating pressure.
Connect supply air to P
Z
.
Connection using female thread G1/4 DIN 45141 or 1/4" NPT:
P
Z
supply air 1.4 to 7 bar
Y1: actuating pressure 1 for single and double-acting actuators
Y2: actuating pressure 2 for double-acting actuators
E: exhaust air outlet; remove the attenuator if required.
For double-acting actuators, connect actuating pressures Y1 or Y2 depending on the
desired safety position. Safety position in case of electrical auxiliary power supply failure:
Y1: single-acting, depressurized
Y1: double-acting, max. actuating pressure/supply air pressure.
Y2: double-acting, depressurized
Note
After installing the pneumatic connections, check the tightness of the entire control
valve. Besides continuous air consumption, the positioner may try to compensate the
position deviation due to leakage. This will lead to premature wear in the entire control
unit.
See also
Changing the operating mode (Page 95)
Pneumatic connection in the flameproof enclosure (Page 26)