Alarm, error, and system messages
11.2 Diagnosis
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
179
11.2.2 Overview of diagnostics values
Explanation about the table
The following table provides an overview of values that can be displayed. The third column
contains the German meaning and the corresponding English term used to derive the
abbreviation if it is not self-explanatory. The last column contains "X" if the value can be set
to zero.
Overview of diagnostics values
No. Abbreviation Meaning Values that can
be displayed
Unit Reset
possibl
e
1 STRKS Stroke number (Strokes) 0 ... 4.29E9 - X
2 CHDIR Changes of direction (Changes of Direction) 0 ... 4.29E9 - X
3 CNT Number of fault messages ( Counter) 0 ... 4.29E9 - X
4 A1CNT Number of alarms 1 (Alarm 1 Counter) 0 ... 4.29E9 - X
5 A2CNT Number of alarms 2 (Alarm 2 Counter) 0 ... 4.29E9 - X
6 HOURS Operating hours (Hours) 0 ... 4.29E9 Hours -
7 WAY Determined actuator travel (Way) 0 ... 130 mm or ° -
8 TUP Actuating time up (Travel Time Up) 0 ... 1000 s -
9 TDOWN Actuating time down (Travel Time Down) 0 ... 1000 s -
10 LEAK Leakage (Leakage) P 0.0 ... 100.0 % -
11 PST Monitoring of the partial stroke test OFF / ###.#, fdini,
notSt, SdtSt,
fdtSt, notd, Strt
s for ###.# -
12 PRPST Time since the last Partial-Stroke-Test ###, notSt, Sdtst,
fdtSt
Days -
13 NXPST Time until the next Partial-Stroke-Test ###, notSt, SdtSt,
fdtSt
Days -
14 DEVI General control valve fault OFF, 0.0 ... 100.0 % -
15 ONLK Pneumatic leakage OFF, 0.0 ... 100.0 - -
16 STIC Static friction/Slipstick effect OFF, 0.0 ... 100.0 % -
17 ZERO Zero point displacement OFF, 0.0 .. 100.0 % -
18 OPEN Displacement of upper end stop OFF, 0.0 ... 100.0 % -
19 PAVG Position average 0.0 ... 100.0 % -
20 P0 Potentiometer value of lower end stop (0%) 0.0 ... 100.0 % -
21 P100 Potentiometer value of upper end stop (100%) 0.0 ... 100.0 % -
22 IMPUP lmpulse length up (Impuls Length Up) 2 ... 160 ms -
23 IMPDN Impulse length down (Impuls Length Down) 2 ... 160 ms -
24 DBUP Dead zone up (Dead Band Up) 0.1 ... 10.0 % -
25 DBDN Dead zone down (Dead Band Down) 0.1 ... 10.0 % -
26 SSUP Slow step zone up (Short Step Zone Up) 0.1 ... 100.0 % -
27 SSDN Slow step zone down (Short Step Zone Down) 0.1 ... 100.0 % -