Technical data
13.1 General technical data
SIPART PS2 with and without HART communications
202 Operating Instructions, 09/2007, A5E00074631-07
General data
Mounting position Any; in wet environment, pneumatic connections and
outlet opening not upward
CE symbol Conformity in regards to EMC guideline 89/336 EEC in
agreement with the following norms
EMC requirements EN 61326/A1 App. A.1 and NAMUR NE21 August 98
Material
Enclosure
6D5**0-*** (plastic) Glass fiber reinforced macrolon
6DR5**1-*** (metal) GD AISi12
6DR5**2-*** (stainless steel) Austenitic stainless steel mat. no. 1.4581
6DR5**5-*** (metal, pressure resistant) GK AISi12
Pressure gauge block
Aluminum AIMgSi, anodized
Vibration resistance
Harmonic vibrations (sine) according to DIN EN 60062-2-
6/05.96
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axle
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axle
Bump (half-sine) according to DIN EN 60068-2-29/03.95
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axle
Noise (controlled digitally) according to DIN EN 60068-2-
64/08.95
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axle
Recommended range of continuous operation of the entire
control valve
≤ 30 m/s² (98.4 ft/s²) without resonance peak
Weight, basic device
Plastic enclosure
Approx. 0.9 kg (1.98 lb)
Metal enclosure, aluminum
Approx. 1.3 kg (2.87 lb)
Metal enclosure, stainless steel
Approx. 3.9 kg (8.6 lb)
Metal enclosure, EEx d version
Approx. 5.2 kg (11.46 lb)
Dimensions See dimensional drawing
Climate class According to DIN EN 60721-3-4
Storage
2
)
1K5, but -40 ... +80°C (1K5, but -40 ... +176°F)
Shipping
2
)
2K4, but -40 ... +80°C (2K4, but -40 ... +176°F)
Operation
3
)
4K3, but -30 ... +80°C (4K3, but -22 ... +176°F)
1
) Impact energy max. 1 joule for plastic/aluminum enclosure.
2
) Be sure that the valves have been flushed out enough with the dry medium when commissioning is at a temperature of
≤ 0°C (≤ 32 F).
3
) When the temperature is ≤ -10°C (≤ 14°F) limited repetition rate of the LCD display When using I
y
modul, only T4 is
permissible.
Certificates and approvals
Classification according to pressure equipment
directive (PED 97/23/EC)
For fluid group 1 gases; fulfills requirements in
article 3, paragraph 3 (good engineering
practice SEP)