4-7
SIMATIC 545/555/575 System Manual
Installing 575 System Hardware
The 16-slot VMEbus base provides space under the lower module guiderails
to install the optional 575 fan assembly (PPX:5752131). The fan assembly
has a switch, located on the rear panel, for selecting 110 or 220 VAC
operation. Before mounting the fan assembly, ensure that the voltage
setting on the fan assembly unit matches your input voltage, and connect
power lines to the AC terminals.
Follow these steps to ensure voltage setting matches input voltage.
NOTE: The fan assembly unit is shipped with the voltage selector switch set
for 110 VAC operation. If your input voltage is 220 VAC, be sure to set the
voltage selection on the unit as described below.
CAUTION
Failure to match voltage selection to your input voltage can result in damage to
the fan assembly unit.
Be sure that the voltage selector switch is set to match your input voltage.
1. Ensure that all power to the system is off before making any changes to
the voltage selector switch (shown in Figure 4-1).
2. To set the voltage, use a flat-bladed screwdriver to rotate the voltage
selector switch to the required position.
110
220
LINE
NEUTRAL
GROUND
AC Power TerminalsVoltage Selector Switch
Figure 4-1 Fan Assembly Rear Panel
To provide power to the fans, follow these steps:
1. Remove the terminal block shield from the AC terminals on the rear
panel.
2. Connect power lines to the AC terminals (shown in Figure 4-1).
3. Replace the terminal block shield.
Selecting Voltage
for Fan Operation
Wiring the AC
Power Terminals