Upgrading Existing Series 500 Installations
C-19
SIMATIC 545/555/575 System Manual
C.6 RS-485/RF I/O Channel Converter
The RS-485/RF (Coaxial) I/O Channel Converter, PPX:5056860, allows you
to use coaxial cables in a Series 505 system, thereby extending the
maximum cable distance to 4 km. The converter connects a Series 505
RS-485 remote I/O interface to an RF remote I/O interface, and makes it
possible to go from a Series 505 local base either to a Series 500 remote base
that has RF media or to a dual media remote base.
For more information about using dual media with Series 505 remote bases,
refer to the SIMATIC 505 Redundant I/O Systems User Manual,
PPX:5058125x.
Your RBC must have firmware Rel. 3.0 or later if you use either the dual
media option or PCS 3.0 or later.
The RS-485/RF I/O channel converter is compatible with the following
CPUs:
5451104 and 5451106 CPUs
5551103, 5551104, 5551105, and 55501106 CPUs
5752104, 5752105, and 5752106 CPUs with installed PPX:5752126
annex card.
NOTE: The RS-485/RF I/O channel converter is compatible only with RBCs
using the Series 505 remote I/O channel and Series 505/Series 500 remote
I/O, such as the PPX:5056850A and PPX:5002114A RF, dual-media-
compatible RBCs. The converter is not compatible with the 505
PROFIBUS-DP RBC or other products that use the PROFIBUS-DP I/O
channel.
Introduction
Compatibility