Cabling and Wiring the System
6-18
SIMATIC 545/555/575 System Manual
Installing Series 505 Remote I/O Cables (continued)
The following procedure assumes you have connected one segment of trunk
line to a terminal block, and wish to add a second segment in order to
extend your installation. Refer to Figure 6-10.
1. Loosen the three terminal screws on terminal block A and install the
second set of cable terminal lugs onto the terminal block.
NOTE: Ensure that the wires of the second set of terminal lugs match with
those of the first set: e.g., if a wire at a terminal screw is blue, the second
wire installed on the same terminal screw must also be blue.
2. Tighten screws on terminal block A.
3. Loosen three screws on terminal block B.
4. Install the terminal lugs on the other cable end to the terminal screws
in terminal block B.
5. Tighten screws on terminal block B.
6. If you are not using another terminal block, install a terminating
resistor across the terminal screws that secure the cable wires with the
color-coded insulation. The terminating resistor value depends on the
type of cable being used, and must match the characteristic impedance.
See Table 6-3. A terminating resistor must be installed on the end
terminal block(s).
Refer to Chapter 9 for procedures to check for faulty cables.