2-20
Pre-installation Guidelines SIMATIC 545/555/575 System Manual
Grounding the Power System (continued)
Cabling at the rear of the unit can be routed in and out of the cabinet
through the two cable ducts at the bottom of the unit or by removing the
break-away tab on the rear panel. (Refer to Figure 4-31 for location of the
break-away tab.)
A ground connector mounted on the side panel of the chassis provides an
earth-ground connection to the chassis. For an alternate location, you can
move the ground lug to the rear mounting bracket, as shown in Figure 2-14.
Ground
Lug
Optional
Mounting
Location
Rear
Mounting
Bracket
Figure 2-14 Grounding Connection and Alternate Location
Use the ground connection (Figure 2-14) to attach one end of a ground wire;
attach the other end to a nearby grounding rod that meets all electrical
specifications required for an earth ground. Use the shortest possible length
of #8 gauge copper wire, or equivalent braided cable, to make the
connection.
If the system is mounted in a cabinet or rack, use the same grounding
procedure. Ensure that a good cabinet or rack ground connection is achieved
by removing existing paint and attaching a #8 gauge copper wire (or
equivalent) using a bolt, washers, and nut as necessary.
Cable
Management for
the 575
Grounding the 575
Controller Chassis
Grounding the
Cabinet or Rack