4-28
Installing 575 System Hardware SIMATIC 545/555/575 System Manual
4.11 Installing a Remote I/O Annex Card (Optional)
There are two ways to connect your 575 CPU to remote I/O:
Use a PPX:5752126 remote I/O annex card to connect the 575 CPU to
Series 505 remote I/O by means of the Series 505 remote I/O channel.
Alternatively, you can use a PPX:505CP5434DP PROFIBUS-DP
annex card to connect the 575 CPU to DP and Series 505 I/O by means
of the PROFIBUS-DP I/O channel.
You can only use one remote I/O annex card per 575 CPU.
The Series 505 remote I/O and PROFIBUS-DP annex cards use a dipswitch
for configuration when used with the 5752104 CPU only. When used with
the 5752105/2106 CPUs, configuration is done with the dipswitch located
on the CPU. Refer to Section 4.10 for details on configuration.
Figure 4-16 shows the location of the dipswitch on the 5752126 annex card.
Figure 4-17 shows the location of the dipswitch on the 505CP5434DP
annex card.
The installation of a remote I/O annex card has an effect on the power
consumption of the CPU. See Table B-2 to calculate power requirements for
Series 505 remote I/O and PROFIBUS-DP I/O annex cards.
If you have made allowances for the effects of annex card power
consumption on your system, you are ready to install your Series 505
remote I/O or PROFIBUS-DP annex card.
Configuring Annex
Card Dipswitch
Annex Card Power
Consumption