4-52
Installing 575 System Hardware SIMATIC 545/555/575 System Manual
Using Boards in the VMEbus Base (continued)
Table 4-6 Use of VME Address Space
Function A24 Address Range A16 Address Range Notes
Primary 575 (Application A) 000000
16
– 0FFFFF
16
0000
16
– 000F
16
1
Secondary 1 (Application B) 100000
16
– 1FFFFF
16
0010
16
– 001F
16
1
Secondary 2 (Application C) 200000
16
– 2FFFFF
16
0020
16
– 002F
16
1
Secondary 3 (Application D) 300000
16
– 3FFFFF
16
0030
16
– 003F
16
1, 2
.
.
.
.
.
.
.
.
.
1,2
Secondary 14 (Application O) E00000
16
– EFFFFF
16
00E0
16
– 00EF
16
1, 2
Reserved — 00F0
16
– 00FF
16
—
575 VMEbus I/O Module 1 F00000
16
– F0FFFF
16
0100
16
– 0101
16
3
575 VMEbus I/O Module 2 F10000
16
– F1FFFF
16
0102
16
– 0103
16
3
.
.
.
.
.
.
.
.
.
3
575 VMEbus I/O Module 16 FF0000
16
– FFFFFF
16
011E
16
– 011F
16
3
Reserved for 575 VMEbus I/O — 0120
16
– 0123
16
3, 4
Available — 0124
16
– FFFF
16
—
Note 1: If the USER-CONFIGURED option has been selected (see Section 4.10), add the configured A24 base
address to the start and end addresses of the A24 address range and the configured A16 base address
to the start and end address of the A16 address range. Refer to Table 4-3, in Section 4.10.
Note 2: If, after addition of the configured A24 base address, the A24 address range for a 575 secondary
would contain an address greater than EFFFFF
16
, then that 575 secondary cannot be installed.
Note 3: Addresses are fixed. Do not add the A24/A16 base address to these addresses.
Note 4: This address range is used if any 575 VMEbus I/O module is installed.