Siemens SIMATIC TI500 Especificaciones Pagina 249

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 322
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 248
System Specifications
A-4
SIMATIC 545/555/575 System Manual
A.3 575 Power Supply Specifications
Table A-3 575 Power Supply Specifications
PPX:5756660 PPX:5756663
Input Voltage
Range 85132 VAC (110)
85132 VAC (110);
170264 VAC (220)
Input Voltage
Frequency 4763 Hz 4763 Hz
Steady State 5 A rms maximum 8 A rms maximum
Input Current
Peak Inrush
50 A maximum for up to
100 ms
50 A maximum for up to
100 ms
Fuse 8.0 A/250 V, slow-blow, 3 AG 10.0 A/250 V, slow-blow, 3 AG
Power
1
+5 VDC: 125 W;
+12 VDC: 36 W;
12 VDC: 24 W;
V
stdby
(Run mode): 5 W;
+5 VDC: 175 W;
+12 VDC: 72 W;
12 VDC: 48 W;
V
stdby
(Run mode): 5 W;
Output Voltage
Current
+5 VDC: 25 A;
+12 VDC: 3 A;
12 VDC: 2 A;
V
stdby
(Run mode): 1 A
3
;
V
stdby
(Batt. bckp): 100 mA
4
+5 VDC: 35 A;
+12 VDC: 6 A
2
;
12 VDC: 4 A
2
;
V
stdby
(Run mode): 1 A
3
;
V
stdby
(Batt. bckp): 100 mA
4
Dimensions
10.3 H 6.3 D 3.6 W
(262 mm 160 mm 91 mm)
10.3 H 6.3 D 3.6 W
(262 mm 160 mm 91 mm)
Class I, Division 2 temperature rating No special restrictions T4A with fans, T4 without fans
1 The wattage ratings are based on nominal voltage.
2
The load power supplied by the +12 or 12 volt output must not exceed the power supplied by the +5 volt
output (i.e., with a 5 A load on the +5 V, the load current supplied by the +12 or 12 must not exceed 2 A).
3 +5 V current draw must be reduced by the amount of V
stdby
current used.
4
The battery will maintain memory for a time inversely proportional to the current consumed
(e.g., 5 Ah / 4 mA = 52 days, assuming a fully charged battery).