System Specifications
A-2
SIMATIC 545/555/575 System Manual
A.1 Physical and Environmental Specifications
Table A-1 Physical and Environmental Specifications
Models
PPX:5451103 CPU PPX:5451104 CPU
PPX:5451105 CPU PPX:5451106 CPU
PPX:5551103 CPU PPX:5551104 CPU
PPX:5551105 CPU PPX:5551106 CPU
PPX:5752104 CPU
PPX:5752105 CPU
PPX:5752106 CPU
PPX:5056850A/B Coax, Dual Media RBC
PPX:5056851A/B RS-485, Dual Media RBC
PPX:5056870 505 PROFIBUS-DP RBC
Operating temperature
0 to 60° C (32 to 140° F)
Storage temperature
40 to +70° C (40 to 158° F)
Relative humidity 5% to 95% noncondensing
Pollution degree 2, IEC 664, 664A
Vibration Sinusoidal
IEC 68-2-6, Test Fc
0.15mm peak-to-peak, 1057 Hz;
1.0g, 57150 Hz
Random
NAVMAT P9492 or IEC 68234,
Test Fdc with 0.04 g
2
/Hz, 80350 Hz, and
3 dB/octave rolloff, 8020 Hz and
3502000 Hz at 10 min/axis
Impact Shock IEC, 68227, Test Ea; Half sine, 15g 11 ms
Isolation, inputs to controller 1500 Vrms except where specified
Corrosion protection All parts of corrosion-resistant material or plated or
painted as corrosion protection
Electric Noise Immunity
Conducted noise:
Radiated noise:
Electrostatic discharge:
IEC 801, Part 4, Level 3
MILSTD461B, Part 4; CS01, CS02, CS06
IEC 2554, Appendix C
EEC 4517/79 Com(78) 766 Final, Part 4
IEEE 472, 2.5 kV
IEC 801 Part 3, Level 3
MILSTD461B, Part 4; RS01, RS02
IEC 801, Part 2, Level 4 (15 kV)