6-17
Cabling and Wiring the System
SIMATIC 545/555/575 System Manual
To connect a trunk line cable to a terminal block, follow the steps below.
Refer to Figure 6-9.
1. Loosen three terminal screws on the terminal block.
2. Install the terminal lugs at the cable end onto the terminal screws.
NOTE: Throughout your installation, make connections carefully to prevent
wire mismatches. For example, if you have already connected one line, such
as a drop line, to the terminal block, when you attach the trunk line you
must ensure that the wires of the second set of terminal lugs match with
those of the first set of terminal lugs. That is, if a wire at a bottom terminal
screw is blue, the wire on the screw directly above it must also be blue.
3. Tighten the screws on the terminal block.
4. If you are not using another terminal block, install a terminating
resistor across the terminal screws that secure the cable wires with the
color-coded insulation.
NOTE: The terminating resistor value depends on the type of cable being
used, and must match the characteristic impedance. See Table 6-3. A
terminating resistor must be installed on the end terminal block(s).
Trunk line
Terminating
Resistor
Figure 6-9 Connecting Trunk Line to Terminal Block
Connecting Trunk
Line Cables