6-21
Cabling and Wiring the System
SIMATIC 545/555/575 System Manual
Standard PROFIBUS-DP cable, connectors, and repeaters are available
from Siemens to cable and wire your installation. The components listed in
Table 6-4 are recommended for all installations. They support baud rates
from 9.6 kbaud through 12 Mbaud.
Table 6-4 PROFIBUS-DP Components—All Baud Rates
Item Order Number Comment
Cable 6XV1 830–0AH10
Connector 6ES7 972–0BA10–0XA0
Connector 6ES7 972–0BB10–0XA0 Includes PG port
Repeater 6ES7 972–0AA00–0XA0
Table 6-5 lists alternate-choice components, for use only in low baud-rate
applications ranging between 9.6 kbaud and 1.5 Mbaud.
Table 6-5 PROFIBUS-DP Components—Low Baud Rates
Item Order Number Comment
Connector 6ES5 762–2AA12
Connector 6ES5 762–2AA21 Includes PG port
Repeater 6GK1 5100–AC00 24 VDC
Repeater 6GK1 5100–AD00
Equipment Needed