Cabling and Wiring the System
6-22
SIMATIC 545/555/575 System Manual
Installing PROFIBUS-DP I/O Cables (continued)
Table 6-6 lists the PROFIBUS DIN 19245 cable line specifications.
Table 6-6 PROFIBUS-DP Cable Specifications
Parameter Value
Impedance 135–165 Ohm (3–20 MHz)
Capacitance 9.1 pF/ft. (<30 nF/km)
Resistance
33.5 W/1000 ft. (<110 Ohm/km)
Attenuation 0.27 dB/100 ft. (0.9 dB/100 m (f=200kHz))
Conductor Area 20–22 AWG (0.3 mm
2
... 0.5 mm
2
)
Cable Diameter 0.315 in. " 0.02 in. (8 mm " 0.5 mm)
Up to 10 bus segments can be connected in series. The distance between the
two most widely separated stations must not exceed the appropriate value
shown in Table 6-7. Use repeaters between each cable segment.
Table 6-7 PROFIBUS-DP Line Length Limits
Baud Rate
Maximum Segment
Length
Maximum Installation
Length
9.6 to 93.75 kbaud 3,930 ft. (1,200 m) 39,300 ft. (12,000 m)
187.5 kbaud 3,280 ft. (1,000 m) 32,800 ft. (10,000 m)
500 kbaud 1,310 ft. (400 m) 13,100 ft. (4,000 m)
1.5 Mbaud 660 ft. (200 m) 6,600 ft. (2,000 m)
3 to 12 Mbaud 330 ft. (100 m) 3,300 ft. (1,000 m)
PROFIBUS-DP Cable
and Connector
Specifications
PROFIBUS-DP Line
Length Limits