5-7
Installing Remote Base Controllers—RBCs
SIMATIC 545/555/575 System Manual
Outputs off
(default)
Freeze
JP6
OFF/FRZ Jumper (JP6)
Dipswitch (SW2) for
setting baud rate
Figure 5-4 Off/Freeze Jumper Location on the –A Model RBCs
Dipswitch (S2) for
setting baud rate
OFF/FRZ Jumper (JP6)
Outputs off
(default)
Freeze
JP6
Switch
1 2 3 4
1 1 0 1
1 1 1 1
0 1 1 1
1 0 1 1
0 0 1 1
Baud Rate
19200
9600
2400
1200
300
Figure 5-5 Position of OFF/FRZ Jumper and Baud Rate Switch on the –B Model RBCs