2-6
Pre-installation Guidelines SIMATIC 545/555/575 System Manual
2.3 575 Fault Relay Operation
The 575 CPU provides a normally open (NO) relay output (fault relay) for
use in a low-voltage safety chain. The CPU must successfully complete
power-up diagnostics before its fault relay is closed. If an error is detected
by the software or the hardware, then the fault relay does not close. During
normal operation, the fault relay remains closed. The fault relay opens if a
fatal error is detected by the 575 CPU. See Figure 4-22 for fault relay
pinouts.
Table 2-1 lists the electrical specifications of the fault relay output.
Table 2-1 Fault Relay Output Electrical Specifications
Features Description
Contact-to-contact breakdown voltage 120 VAC
Contact-to-ground breakdown voltage 500 VAC
Voltage rating 30 V, AC or DC
Current rating
500 mA resistive AC or DC
200 mA inductive DC (L/R = 7 ms)
100 mA inductive AC (power factor > 0.4)
The 575 CPU fault relay is under software control. The operating system
software can be in one of three states: Idle, Normal, or Fault. The fault relay
closes only when the software state is Normal. The transitions to and from
the various states are described in this section and are shown in Figure 2-4.
Idle State
Fault relay operation begins in the Idle state and transitions to one of two
states. The fault relay transitions to the Fault state if a fault is detected
during CPU initialization, or if you perform a battery-good powerup in fault
mode. Otherwise, the fault relay transitions to the Normal state.
Normal State
The fault relay can transition to either the Idle state or the Fault state from
the Normal state. If power is turned off, the fault relay transitions to the
Idle state. If a fatal error is detected, the fault relay transitions to the Fault
state.