Power and Compatibility
B-5
SIMATIC 545/555/575 System Manual
Table B-3 Series 505 Module Power Requirements (continued)
Model Number
Description
Special
Function
Immediate
Maximum DC Power
Consumption (Watts)
PPX:
Description
Function
Module
I/O
+5 V –5 V
505–6850-A Coax, Dual Media RBC — — 5.0 0.200
505–6850-B Coax, Dual Media RBC — — 5.0 0.200
505–6851-A RS-485, Dual Media RBC — — 5.0 0.200
505–6851-B RS-485, Dual Media RBC — — 5.0 0.200
505–6870 505 PROFIBUS-DP RBC — — 5.0 0.200
505–6860 RF to RS-485 Converter — — 2.0 0.200
505–7002 High Speed Counter & Encoder —
n
2.0 —
505–7003 High Speed Counter Encoder —
n
2.0 —
505–7012 8 In/4 Out Analog —
n
3.0 0.030
505–7016 Bipolar 8 In/4 Out Analog —
n
3.0 0.030
505–7028 Thermocouple Input —
n
2.2 0.01
505–7028-A Thermocouple Input —
n
3.0 0.01
505–7038 RTD Input —
n
2.2 0
505–7101 BASIC Module
n
— 6.0 0.125
505–7190 7MT Channel Controller — — 4.0 —
505–7202 FIM (Field Interface Module) — — 2.5 —
505–7339 NIM (Network Interface Module)
n
— 8.0 —
505–7340 Dual Media NIM
n
— 8.0 —
505–7354 Peerlink
n
— 8.0 —
505–ATM–0220,
–0440, –4120
386/ATM Coprocessor Module
(IBM AT-Compatible Coprocessor)
n
— 11.0 0.200
505–CP1434TF H1 Communication Processor
n
— 22.0
2
0.100
505–CP5434
–FMS
PROFIBUS-FMS Communication
Processor
n
— 5.0 0.200
545–1103
545–1105
Programmable Logic Controller — — 4.0/8.5
3
0.200
545–1104
545–1106
Programmable Logic Controller — — 8.5 0.200
555–1103
555–1104
555–1105
555–1106
Programmable Logic Controller — — 8.5 0.200
1
Modules that are affected by date code restrictions. See Section B.2 for information.
2
Maximum power consumption 22.0 W with jumper E1 installed. Without jumper E1, maximum power
consumption is 10.0 W.
3
Without PROFIBUS-DP annex card/with PROFIBUS-DP annex card.
Note: For any module not listed here, consult the manual for that module.