58
© EPCOS AG 2015
Please read Important notes on page 4 and Cautions and warnings on page 5.
Bitte beachten Sie die Seite 4 Wichtige Hinweise sowie die Warn- und Sicherheitshinweise auf Seite 5.
AC Power Line Protection
Schutz von Wechselspannungsnetzen
Protection class I & II
V13-… D20-… L1B-… H38-…
ø11.8±0.2
17.1±0.5
4.2±0.3
ø21±0.5
Tin-plated
M8
1.5 max.
29.7±0.3
7+0.5
32.7±0.5
48 max.
0.5)(ø15
_
ø30 max.
size
13
Type
Ordering code
V13-A500XN
B88069X6940C251
V13-A800XN
B88069X4380C251
D20-A800XP
B88069X7691B301
L1B-A800XP1
B88069X6551B201
H38-E800XP
B88069X6821B101
Class I & II I & II I & II I I
Application for N-PE N-PE N-PE N-PE N-PE
Nom. DC spark-over voltage V
sdcN
500 800 800 800 800 V
DC spark-over voltage 500 … 850 > 600 > 600 > 600 > 600 V
Front of wave spark-over voltage
@ 1.2/50 µs, 6 kV
< 1300 < 1500 < 1500 < 1500 < 1500 V
Class I
Max. continuous operating
voltage @ 50/60 Hz U
c
255 255 264 264 255 V
Nominal discharge current
8/20 μs I
n
40 40 30 50 100 kA
Impulse current 10/350 μs l
imp
12 12 25 50 100 kA
Follow current @ 50/60 Hz I
f
100 100 100 100 100 A
Class II
Max. continuous operating
voltage @ 50/60 Hz U
c
255 255 264 – – V
Nominal discharge current
8/20 μs I
n
40 40 30 – – kA
Max. discharge
current 8/20 μs l
max
60 60 40 – – kA
Follow current @ 50/60 Hz I
f
100 100 100 – – A
AC discharge current
(TOV at 1200 V)
1 operation 50 Hz, 0.2 s
300 300 300 300 300 A
Insulation resistance > 1 > 1 > 1 > 1 > 1 GΩ
Arresters are designed in accordance with IEC 61643-11
About packing see page 71.