Types with follow current limiting
5 kA / 5 A
l
ø 8 × 6 mm
EF…
ød
ø8±0.2
6±0.2
1
Type
Ordering code
EF270X
B88069X4131S102
EF470X
B88069X5080S102
EF800X
B88069X2641S102
EF1500X
B88069X4301S102
EF2500X
B88069X5690T502
Nom. DC spark-over voltage V
sdcN
270 470 800 1500 2500 V
Tolerance of V
sdcN
–15/+25 –15/+25 –15/+25 ±20 ±20 %
Impulse spark-over voltage
@ 100 V/µs 99% of
measured values
< 500 < 700 < 1200 < 1800 < 3700 V
@ 100 V/µs typical values < 450 < 600 < 1000 < 1700 < 3300 V
@ 1 kV/µs 99% of
measured values
< 550 < 800 < 1300 < 2000 < 4500 V
@ 1 kV/µs typical values < 500 < 700 < 1100 < 1800 < 3700 V
Service life
10 operations 50 Hz, 1 s 5 5 5 5 5 A
1 operation 50 Hz, 9 cycles 65 65 65 35 35 A
10 operations 8/20 µs 5 5 5 5 5 kA
1 operation 8/20 µs 10 10 10 10 10 kA
Max. follow current during one
voltage half cycle @ 50 Hz
200 200 200 200 – A
Insulation resistance > 10 > 10 > 10 > 10 > 10 GΩ
Capacitance @ 1 MHz < 1.5 < 1.5 < 1.5 < 1.5 < 1.5 pF
Lead diameter d
1
1.0 1.0 1.0 1.0 0.8 mm
About packing see page 71.