38
© EPCOS AG 2015
Please read Important notes on page 4 and Cautions and warnings on page 5.
Bitte beachten Sie die Seite 4 Wichtige Hinweise sowie die Warn- und Sicherheitshinweise auf Seite 5.
Light-duty types
5 kA / 5 A
l
ø 5 × 5 mm; 5.7 × 5 × 5 mm
S50-… M50-… M51-…
5±0.3
0.5
Tin-plated
6.4
1.5
5.5
RAB0174-C
5±0.2
ø0.8
ø5±0.2
5±0.2
Type
Ordering code
M51-A75X
B88069X6131C102
M50-C90X
B88069X1590C253
M51-C90X
B88069X5010C102
S50-A90X
B88069X1913T902
M50-A230X
B88069X4600C253
M51-A230X
B88069X2930C102
S50-A230X
B88069X1923T902
M50-A350X
B88069X4630C253
M51-A350X
B88069X4640C102
M51-A600X
B88069X4590C102
Nom. DC spark-over voltage V
sdcN
75 90 230 350 600 V
Tolerance of V
sdcN
±20 ±20 ±20 ±20 –5/+30 %
Impulse spark-over voltage
@ 100 V/µs 99% of
measured values
< 350 < 550 < 550 < 800 < 1350 V
@ 100 V/µs typical values < 300 < 500 < 500 < 750 < 1200 V
@ 1 kV/µs 99% of
measured values
< 650 < 600 < 650 < 900 < 1500 V
@ 1 kV/µs typical values < 550 < 550 < 600 < 800 < 1350 V
Service life
10 operations 50 Hz, 1 s 5 5 5 5 5 A
1 operation 50 Hz, 9 cycles 10 10 10 10 10 A
10 operations 8/20 µs 5 5 5 5 5 kA
1 operation 8/20 μs
1)
10 10 10 10 10 kA
1 operation 10/350 μs 0.5 0.5 0.5 0.5 0.5 kA
300 operations 10/1000 μs 100 100 100 100 – A
Insulation resistance > 1 > 1 > 1 > 1 > 1 GΩ
Capacitance @ 1 MHz < 1 < 1 < 1 < 1 < 1 pF
1)
After loading DC breakdown may exceed initial values but device will remain in a safe mode.
About packing see page 71.