Heavy-duty types
20 kA / 20 A
l
ø 11.8 × 17.4 mm
V10-…
RAB0277-L
32±1
M3
ø11.8±0.2
5.8±0.2
7.3±0.3
17.4±0.5
Type
Ordering code
V10-H08X
B88069X9170C251
V10-H14X
B88069X4300C251
V10-H22X
B88069X4420CB251
V10-H30X
B88069X4330C251
Nom. DC spark-over voltage V
sdcN
800 1400 2200 3000 V
DC spark-over voltage ±20 ±20 ±20 ±25 %
Impulse spark-over voltage
@ 100 V/µs 99% of
measured values
< 1000 < 1900 < 2700 < 4500 V
@ 100 V/µs typical values < 900 < 1800 < 2400 < 4300 V
@ 1 kV/µs 99% of
measured values
< 1200 < 2200 < 2800 < 5000 V
@ 1 kV/µs typical values < 1100 < 2000 < 2500 < 4500 V
Service life
10 operations 50 Hz, 1 s 20 20 20 20 A
1 operation 50 Hz, 9 cycles 120 120 120 120 A
10 operations 8/20 µs 20 20 20 20 kA
1 operation 8/20 µs 30 30 25 25 kA
1 operation 10/350 µs 5 kA
Insulation resistance > 10 > 10 > 10 > 10
Capacitance @ 1 MHz < 1.5 < 1.5 < 1.5 < 1.5 pF
About packing see page 71.
2-Electrode Arresters
2-Elektroden-Ableiter