42
© EPCOS AG 2015
Please read Important notes on page 4 and Cautions and warnings on page 5.
Bitte beachten Sie die Seite 4 Wichtige Hinweise sowie die Warn- und Sicherheitshinweise auf Seite 5.
Heavy-duty types
20 kA / 20 A
l
ø 8 × 20 mm
A83-…
6.05±0.2
20±0.5
ø7.6±0.2
+0.2
0.4
ø8
_
Type
Ordering code
A83-C90X
B88069X
1450C102
A83-A150X
B88069X
4350C102
A83-A170X
B88069X
4360C102
A83-A230X
B88069X
1420C102
A83-A350X
B88069X
2860C102
A83-A600X
B88069X
2890C102
Nom. DC spark-over voltage V
sdcN
90 150 170 230 350 600 V
Tolerance of V
sdcN
±20 ±20 ±20 ±20 ±20 ±20 %
Impulse spark-over voltage
@ 100 V/µs 99% of
measured values
< 500 < 600 < 650 < 550 < 700 < 1100 V
@ 100 V/µs typical values < 450 < 450 < 500 < 450 < 650 < 950 V
@ 1 kV/µs 99% of
measured values
< 600 < 800 < 800 < 700 < 800 < 1400 V
@ 1 kV/µs typical values < 550 < 600 < 600 < 550 < 700 < 1100 V
Service life
10 operations 50 Hz, 1 s 20 20 20 20 20 20 A
1 operation 50 Hz, 9 cycles 100 100 100 100 100 100 A
10 operations 8/20 µs 20 20 20 20 20 20 kA
1 operation 8/20 µs 25 25 25 25 25 25 kA
1 operation 10/350 µs 2.5 2.5 2.5 2.5 2.5 2.5 kA
Insulation resistance > 10 > 10 > 10 > 10 > 10 > 10 GΩ
Capacitance @ 1 MHz < 1.5 < 1.5 < 1.5
< 1.5 < 1.5 < 1.5 pF
About packing see page 71.
2-Electrode Arresters
2-Elektroden-Ableiter
Comentarios a estos manuales