Configuring alarm inputs
79
Siemens Building Technologies
Fire Safety & Security Products 03.2009
11.3 Configuring network alarm inputs
11.3.1 Configuring priority
The following priorities can be selected for alarm inputs:
z Normal (the alarm input icon in the alarm input list is red)
z Hold-up (the alarm input icon in the alarm input list is orange)
z Suspicion (only possible if bank mode is active; the alarm input icon in the alarm
input list is purple)
The priority of an alarm input plays a role in the configuration of the recording. See
Section
1101H16.4 1102HConfiguring recording modes. When an alarm with the priority hold-up
is triggered, active recordings with the normal alarm priority and movement
recordings are automatically ended. However, active recordings with the hold-up
alarm priority cannot be automatically ended.
Fig. 70 Priority group field on the Alarm input tab
1. Select the Alarm input tab.
2. Select the alarm input you want to configure in the list.
3. Select the priority of the alarm input in the Priority group field.
11.3.2 Configuring time control
You can activate and deactivate alarm inputs under time control.
Alarm inputs with the priority hold-up or suspicion cannot be activated or deactivated with time control.
Fig. 71 Time control checkbox on the Alarm input tab
1. Select the Alarm input tab.
2. Select the alarm input you want to configure in the list.
3. Mark the checkbox Time control.
4. Click Options....