Page 54 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Pump Control
Other Pump Control Algorithms
Set Relays to ALTERNATE DUTY BACKUP
Set the Relay ON Setpoints
Set the Relay OFF Setpoints
Set Relays to FIXED DUTY ASSIST
Set the Relay ON Setpoints
Set the Relay OFF Setpoints
Parameter Index Value Description
P111 1 53
Sets the pump relays (index 1, 2, and 3) to
ALTERNATE DUTY BACKUP.
P111 2 53
P111 3 53
Parameter Index Value Description
P112 1 0.4m Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
Subsequent cycles rotate the setpoints
among the pumps.
P112 2 0.3m
P112 3 0.2m
Parameter Index Value Description
P113 0 1.3m By using index 0 all HydroRanger 200 are set
at the same time, including any alarm relays.
Use with caution.
Parameter Index Value Description
P111 1 50 Sets the pump relays (index 1, 2, and 3) to
FIXED DUTY ASSIST. Multiple pumps can run
simultaneously.
P111 2 50
P111 3 50
Parameter Index Value Description
P112 1 0.4m Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
Subsequent cycles rotate the setpoints
among the pumps.
P112 2 0.3m
P112 3 0.2m
Parameter Index Value Description
P113 0 1.3m By using index 0 all HydroRanger 200 are set
at the same time, including any alarm relays.
Use with caution.