7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 189
mmmmm
Parameters
P803 Shot / Pulse Mode
Determines what type of ultrasonic shots are fired.
Use this feature to increase HydroRanger 200 response when the monitored surface is
close to the transducer face. Select short and long to have short and long acoustic shots
fired for each measurement, regardless of the transducer to surface distance.
Select short to have only short shots fired if the Echo Confidence (P805) produced by a
short shot exceeds the short Confidence Threshold (P804) and the monitored surface is
always within the Short Shot Range (P852).
P804 Confidence Threshold
Determines which echoes are evaluated by software.
Use this feature when an incorrect material level is reported. The short and long shot
Confidence Thresholds are preset to 10 and 5 respectively. When Echo Confidence (P805)
exceeds the Confidence Threshold, the echo is evaluated by Sonic Intelligence®. Values
are entered as two numbers separated by a decimal point. The first number is the short
shot confidence and the second number is the long shot confidence.
Primary Index Global
Values
1Short
2 * Short and long
Related
P006 Empty
P805 Echo Confidence
P804 Confidence Threshold
P852 Short Shot Range
Primary Index Global
Values
Range: 0 to 99:0 to 99
Preset: 10:5
Related P805 Echo Confidence
Note: The decimal point is replaced with a colon (:) on the display.