7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 137
mmmmm
Parameters
P170 Flush Pump
Picks the number of the pump relay which triggers the flushing device.
Enter the relay number of the pump with the flush valve. The activation of this pump relay
drives the usage of the flush system. Both P172 Flush Interval and P171 Flush Cycles are
based on the operation of this relay and controls any relay set to P111 = 64, Flush Valve.
P171 Flush Cycles
Sets the number of pump cycles requiring flush control.
If three flush cycles are required after every ten pump cycles then:
P172 (Flush Interval) = 10
P171 (Flush Cycles) = 3
P172 Flush Interval
Sets the number of pump cycles before flush control is enabled
To start a new flush cycle every ten times the pumps are run, set this to 10.
Primary Index Global
Values
Range: 0 to 6
Preset: 0
Related • P111 = 64, Flush Valve
Primary Index Global
Values
Range: 0 to 9999
Preset: 0
Related • P111 = 64, Flush Valve
Primary Index Global
Values
Range: 0 to 9999
Preset: 0
Related • P111 = 64, Flush Valve