
Page 154 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P332 Auto Record Transducer
Specifies the Transducer Point Number for which Auto Profile Records are saved.
This feature is preset to Point Number 1. (Alteration is only required if differential or
average Operation [P001 = 4 or 5] is selected.)
P333 Auto Record Interval
Enter the time to elapse after an Auto Profile Record is saved before another Auto Profile
Record can be saved (subject to all other restrictions).
Auto Record ON and OFF Setpoints (P334 to P337)
Use Auto Record ON Setpoint (P334) and Auto Record OFF Setpoint (P335) to define the
boundaries within which the level must be, for the resultant Echo Profile to be considered
for an Auto Profile Record.
If ---- is displayed for either P334 or P335, Auto Profile Records are saved regardless of
current level (subject to all other restrictions).
Enter the level value in Units (P005) or percent of Span (P007) as referenced to
Empty (P006).
Primary Index Global
Values
Range: 0 to 2
0 Any transducer
1* Transducer One
2Transducer Two
Altered By • P001 Operation = 4 or 5
Primary Index Global
Values
Range: 0.0 to 9999 (minutes)
Preset: 120
Comentarios a estos manuales