Page 12 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Wiring
Terminal Board
The terminal board on the HydroRanger 200 allows all inputs and outputs to be connected
simultaneously.
Cables
The HydroRanger 200 transceiver requires a shielded two-wire connection to the
transducer.
Connection Cable Type
mA input and mA output
sync, Temperature sensor,
discrete input, dc input
Transducer
2-3 copper conductors, twisted, with shield
1
, drain wire,
300V 0.5-0.75 mm
2
(22 - 18 AWG).
Maximum length: 365m
1.
Preferred shielding is braided screen.
Do not use a coaxial transducer cable extension with the
HydroRanger 200. Electrical noise interference affects
performance.
Relay output
ac input
Relay to be copper conductors per local requirements to
meet 250V 5A contact rating.
Note: Recommended torque on terminal clamping screws.
• 0.56 - 0.79 Nm
• 5 - 7 in.lbs
Please do not overtighten the screws.
L2/N L1
TB1
TB3
TB2
RELAY 1
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
2
1
mA INPUT
SHIELD
SYNC
1
2
4 - 20 mA
OUTPUTS
TS-3
SHIELD
1
2
DISCRETE
INPUTS
RS485
B
A
COM
12-30 V
TB1
DC Version