Siemens HydroRanger 200 Manual de instrucciones Pagina 211

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 256
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 210
7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 197
mmmmm
Parameters
Advanced TVT Adjustment (P830 to P835)
The following parameters are for authorized Siemens Milltronics Service personnel or
technicians familiar with Siemens Milltronics echo processing techniques.
Advanced TVT control applies to long shots only.
P830 TVT Type
Selects the TVT Curve used.
Select the TVT type giving the highest confidence (P805) under all level conditions. Use
this parameter with caution. Do not use TVT Slopes with the bF or bLF Algorithm (P820).
P831 TVT Shaper
Turns the TVT Shaper ON or OFF.
Turn the TVT Shaper ON before and after using P832. Turn the TVT Shaper ON and OFF
while monitoring the effect to pick up the true echo.
Primary Index Global
Values
1 TVT Short Curved
2 TVT Short Flat
3TVT Long Flat
4 TVT Long Smooth Front
5 TVT Long Smooth
6TVT Slopes
Altered By •P002 Material
Related
P805 Echo Confidence
P835 TVT Slope Min
Primary Index Global
Values
0*off
1on
Related P832 TVT Shaper Adjust
Vista de pagina 210
1 2 ... 206 207 208 209 210 211 212 213 214 215 216 ... 255 256

Comentarios a estos manuales

Sin comentarios