Page 180 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
This feature may only be used to adjust the delay before the next point is scanned. Enter
the amount of delay in seconds. This value is automatically altered when Maximum
Process Speed (P003) is altered.
P728 Shot Delay
The delay, in seconds, between transducer shots.
Use this if transient acoustic noise within the vessel causes measurement difficulties due
to echoes from one shot being received on the next. If more than one ultrasonic unit is
installed for redundancy, this value should be 0.
P729 Scan Time
View the elapsed time (in seconds) since the point displayed was last scanned.
This may be viewed as an Auxiliary Reading in the RUN mode.
Display (P730 to P739)
P730 Auxiliary Reading
Use this feature to display operator selected Auxiliary Readings temporarily or
indefinitely (as desired).
Select OFF to display Auxiliary Readings temporarily. Select HOLd to display Auxiliary
Readings until another Auxiliary Reading is selected or programming mode is entered.
See the
Hand Programmer
section on page 22 for RUN mode auxiliary readings.
Primary Index Transducer
Values
Range: 0.1 to 4.0
Preset: 0.5
Primary Index Level Point
Values Range: 0.000 to 9999 (view only)
Related • P001 Operation
Primary Index Global
Values
Range: 000 to 999
Display: OFF, HOLd