Wiring
Level System Synchronization
When using multiple ultrasonic level monitors, be sure to run the transducer cables in
separate grounded metal conduits.
When separate conduits are not possible, synchronize the level monitors so that no unit
transmits while another is waiting for echo reception.
Synchronizing with another HydroRanger 200 or other Milltronics instru-
ments (DPL+, SPL, XPL+, Hydro+, EnviroRanger, MiniRanger, MultiRanger
100/200):
• Mount the level monitors together in one cabinet
• Use a common power (mains) supply and ground (earth) for all units
• Interconnect the SYNC terminals of all level monitors
• Contact Siemens Milltronics or your local distributor. See www.milltronics.com.
Power
Note: The HydroRanger 200 CANNOT be synchronized with the MultiRanger Plus or
the HydroRanger.
HydroRanger
Other Siemens
Important!
Before applying power to the HydroRanger 200 for the first time, ensure any
connected alarm/control equipment is disabled until satisfactory system operation
and performance is verified.
Notes for AC power connections
• The equipment must be protected by a 15 A fuse, or circuit breaker in the
building installation.
• A circuit breaker or switch in the building installation, marked as the disconnect
switch, must be in close proximity to the equipment and within easy reach of the
operator.
L1
L2/N
GND
Note: Make sure unit is
connected to a
reliable ground.
Ground