Page 130 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P118 Relay Output Logic
The logic applied to relays to determine the contact open or closed state.
The relay contact operation is NORMALLY CLOSED for alarms and NORMALLY OPEN for
controls. See P111
Relay Control Function
for more information.
Power Failure
When power is cut to the HydroRanger 200, its relays fail to the following states:
To use relays 3 or 6 as general alarm indicators, set P118 to 3 – negative logic and wire
the alarm for normally open operation. When an alarm event occurs (see below) or when
power is cut, the circuit closes and the alarm activates.
Positive Logic
In software, all relays are programmed the same way, with ON setpoints indicating when
to change the relay contact state (open or closed). This parameter allows the reversal of
the operation so that relay contacts can be NORMALLY CLOSED or NORMALLY OPEN.
P118 is preset to 2 which is positive logic.
Negative Logic
When P118 = 3 (negative logic), the operation for the indexed relay is reversed from
normal.
Primary Index Relay
Values
Value Logic
Alarm
Contact
Pump or Control
Contact
2 * Positive Normally Closed Normally Open
3 Negative Normally Open Normally Closed
Related P111 Relay Control Function
Relay States
Relay Fail State
1,2,4,5 Open
3,6
Open or Closed
1
1.
Relays 3 and 6 are Form C types, so you can wire it either NORMALLY
OPEN or NORMALLY CLOSED. Check the wiring before programming.