Siemens HydroRanger 200 Manual de instrucciones Pagina 134

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 256
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 133
Page 120 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P054 Level Breakpoints (Universal Volume Calculation)
When the tank shape is too complex for any of the preconfigured shapes, you can specify
the volume based on segments.
Enter the following:
up to 32 level breakpoints (where volume is known) if P050 = 9 or 10
Entering a Level Breakpoint
1. Go to Parameter P054.
2. For each index enter a breakpoint in measurement units.
3. Ensure that each breakpoint corresponds to the same index for P055.
P055 Volume Breakpoints and Characterization
(Universal Volume Calculation)
Each segment defined by the level breakpoints (P055) requires a volume so that the
HydroRanger 200 can make the level-to-volume calculations.
Typical volume calculations
Primary Index Global
Secondary Index Breakpoint
Values Range: 0.0 to 9999
Related P055 Volume Breakpoints
Primary Index Global
Secondary Index Breakpoint
Values Range: 0.0 to 9999
Related P054 Breakpoints Levels (Universal Volume Calculation)
Cone Cylinder
V = (1/3)πr
2
hV = πr
2
h
Vista de pagina 133
1 2 ... 129 130 131 132 133 134 135 136 137 138 139 ... 255 256

Comentarios a estos manuales

Sin comentarios