Siemens HydroRanger 200 Manual de instrucciones Pagina 127

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 256
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 126
7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 113
mmmmm
Parameters
P000 Lock
Secures the HydroRanger 200 from changes.
Access this parameter directly (type 000) and enter any value (except 1954) to secure
programming lock. To unlock the HydroRanger 200, access this parameter and enter 1954.
Quick Start (P001 to P007)
P001 Operation
Sets the type of measurement required for the application.
For DPD and DPA Programming
For Dual Point Difference (DPD) or Dual Point Average (DPA), the unit requires either two
transducers of the same type, or one transducer and one mA input. If two transducers are
used, all transducer parameters become indexed, and a third level point is calculated.
DPD (difference) = Point 1 - Point 2
DPA (average) = (Point 1 + Point 2) / 2. The calculated DPD or DPA is always based
on level measurements of points 1 and 2.
Primary Index Global
Values
1954 * OFF (programming permitted)
-1
Simulation Controls (relays energize based on simu-
lated level)
other lock activated (programming secured)
Related Simulation
Primary Index Global
Values
0Out-of-service
1 Level – how full the vessel is. (Volume – P050)
2 Space – how empty the vessel is (ullage – P050)
3 * Distance – distance from transducer to material
4 DPD – dual point difference
5 DPA – dual point average
6 OCM – flow rate in an open channel
7 Pump Totalizer – total pumped volume
Alters P600 Primary Measuring Device
WARNING:
Use this lock as backup security only. It uses a fixed value which can be
discovered by unauthorized personnel.
Vista de pagina 126
1 2 ... 122 123 124 125 126 127 128 129 130 131 132 ... 255 256

Comentarios a estos manuales

Sin comentarios