Ladder Logic (LAD) for S7-300 and S7-400
C79000-G7076-C504-02
3.8 Basic Guidelines for Entering Ladder Logic Instructions
A Ladder network can contain several elements in different branches. All
elements and branches must be connected together; however, the power rail
on the left does not count as a connection (IEC 1131-3).
When you program in Ladder, you must observe certain guidelines.
Any errors are reported with an error message in the Program Editor.
Every Ladder network must end with a coil or a box. You cannot use the
following elements to close a network:
S Comparison boxes
S Midline outputs (#)
S Positive (P) or Negative (N) RLO edge detection
Branches that cause reverse power flow (from right to left) cannot be edited.
Figure 3-8 shows an example. With signal state “0” at I 1.4, a power flow
from right to left would be possible at I 6.8. This is not allowed.
I 1.0
Q 2.6
I 1.2 I 1.4 I 4.2
I 6.8
Q 4.4 I 2.8
Q 6.0
✗
Illegal Power Flow
Figure 3-8 Power Flow in Reverse Direction (Illegal)
Overview
Ending a Ladder
Network
Power Flow
Creating Logic Blocks