Siemens NAN 67 Series Manual de servicio Pagina 248

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 318
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 247
20-14
Ladder Logic (LAD) for S7-300 and S7-400
C79000-G7076-C504-02
When the MCRA instruction activates the MCR function, you can create up to eight nested MCR
zones. In the example, there are two MCR zones. The first MCR> instruction works together with the
second MCR< instruction. All instructions between the second set of MCR brackets (MCR<MCR>)
belong to the second MCR zone. The operations are executed as follows:
S If the signal state of input I 0.0 = 1, the signal state of input I 0.4 is assigned to output Q 4.1.
S If the signal state of input I 0.0 = 0, the signal state of output Q 4.1 is 0 regardless of
the signal state of input I 0.4. Output Q 4.0 remains unchanged regardless of the signal state
of input I 0.3.
S If the signal state of input I 0.0 and I 0.1 = 1, output Q 4.0 is set to 1 if the signal state
of input I 0.3 is 1 and output Q 4.1 = input I 0.4.
S If the signal state of input I 0.1 = 0, output Q 4.0 remains unchanged regardless of
the signal state of input I 0.3 and input I 0.0.
I 0.0
I 0.1
I 0.3
Q 4.0
Status Word Bits
BR CC 1 CC 0 OV OS OR STA RLO FC
Write 0 1 0
S
I 0.4
MCR>
MCRD
MCR <
MCRA
MCR>
Q 4.1
MCR <
Figure 20-8 Master Control Relay Off
Program Control Instructions
Vista de pagina 247
1 2 ... 243 244 245 246 247 248 249 250 251 252 253 ... 317 318

Comentarios a estos manuales

Sin comentarios