20-8
Ladder Logic (LAD) for S7-300 and S7-400
C79000-G7076-C504-02
20.4 Master Control Relay Instructions
The Master Control Relay (MCR, see also Section 20.5) is an American relay
ladder logic master switch for energizing and de-energizing power flow
(current path). A de-energized current path corresponds to an instruction
sequence that writes a zero value instead of the calculated value, or, to an
instruction sequence that leaves the existing memory value unchanged.
Operations triggered by the instructions shown in Table 20-4 are dependent
on the MCR.
The Output Coil and Midline Output instructions write a 0 to the memory if
the MCR is 0. The Set Coil and Reset Coil instructions leave the existing
value unchanged (see Table 20-5).
Table 20-4 Instructions Influenced by an MCR Zone
Element or Name in Box Instruction Name Section in This
Manual
#
Midline Output 8.5
Output Coil 8.4
S
Set Coil 8.8
R
Reset Coil 8.9
SR
Set_Reset Flipflop 8.22
RS
Reset_Set Flipflop 8.23
MOVE
Assign a Value 14.1
Table 20-5 Operations Dependent on MCR and How They React to Its Signal State
Signal State of
MCR
Output Coil or
Midline Output
#
Sector Set or Reset
SR RS
S
R
Assign a Value
MOVE
0
Writes 0
(Imitates a relay that falls to its
quiet state when voltage is
removed)
Does not write
(Imitates a latching relay that
remains in its current state
when voltage is removed)
Writes 0
(Imitates a component that, on
loss of voltage, produces a
value of 0)
1 Normal execution Normal execution Normal execution
Definition of
Master Control
Relay
Program Control Instructions