3-11
Ladder Logic (LAD) for S7-300 and S7-400
C79000-G7076-C504-02
3.6 Assigning System Attributes for Parameters
You can assign system attributes to blocks and parameters. These influence
the message and connection configuration, operator interface functions, and
process control configuration.
You can assign system attributes for parameters in the variable declaration
table.
To enter system attributes for parameters, select the name of the parameter in
the variable declaration table and select Edit
"
Object Properties in the
menu bar to display the Properties dialog. Select the “System Attributes”
tabbed page and enter the required attribute and its value.
Table 3-3 shows which system attributes you can enter in the variable
declaration table.
Table 3-3 System Attributes for Parameters
Attribute Value When to Assign the Attribute Permitted
Declaration type
S7_server connection, alarm_archiv When the parameter is relevant to connection or
message configuration. This parameter contains
the connection or message number.
IN
S7_a_type alarm, alarm_8,
alarm_8p, alarm_s,
notify, ar_send
When the parameter will define the message
block type in a message block (only possible
when the S7_server attribute is set to
alarm_archiv).
IN, only with blocks
of the type FB and
SFB
S7_co pbkl, pbk, ptpl, obkl, fdl,
iso, pbks, obkv
When the parameter will specify the connection
type in the connection configuration (only
possible when the S7_server attribute is set to
connection).
IN
S7_m_c true, false When the parameter will be modified or
monitored from an operator panel.
IN/OUT / IN_OUT,
only with blocks of
the type FB and SFB
S7_shortcut Any 2 characters, for
example, W, Y
When the parameter is assigned a shortcut to
evaluate analog values.
IN/OUT / IN_OUT,
only with blocks of
the type FB and SFB
S7_unit Unit, for example, liters When the parameter is assigned a unit for
evaluating analog values.
IN/OUT / IN_OUT,
only with blocks of
the type FB and SFB
System Attributes
Entering System
Attributes for
Parameters
Creating Logic Blocks