ET 200S in the PROFIBUS Network
4-2
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
4.1 ET 200S in the PROFIBUS network
Structure of a PROFIBUS network
The figure below illustrates the basic structure of a PROFIBUS network with one
DP master and several DP slaves.
0 ... 7 PROFIBUS addresses of the nodes
S7-300
(DP master)
ET 200S
7
0
3
4
5
1
ET 200S
ET 200M
* The ET 200S can be configured and programmed from this PD
2
PD*
OP 25**
6
** Operating and monitoring functions can be executed on the ET 200S
ET 200X
ET 200X
Figure 4-1 Example of a PROFIBUS network
Hardware prerequisites in the PD/OP for accessing the ET 200S
Before you can access an IM 151-7 CPU from a PD/OP, the PD/OP must fulfill the
following requirements:
it must have an integrated PROFIBUS-DP interface or DP card; or
it must have an integrated MPI interface or MPI card.
Data transfer rates over 1.5 MBaud require an active connecting cable for the PD
connection.