Addressing
3-10
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
User Data Transfer in STOP Mode
The user data in the intermediate memory is processed differently depending on
whether the DP master or the DP slave (IM 151-7 CPU) goes into STOP mode.
If the IM 151-7 CPU goes into STOP mode: The data in the intermediate
memory (outputs only from the slaves viewpoint) of the IM 151-7 CPU are
overwritten with “0”; i.e. the DP master or a recipient in direct communication
reads “0”.
If the DP master goes into STOP mode: The current data in the intermediate
memory of the IM 151-7 CPU (inputs in the slave, outputs in the master) are
retained and can be read out in the user program of the IM 151-7 CPU.
S5 DP master
If you use the IM 308C as a DP master and the IM 1517 CPU as an I slave, the
following applies to the exchange of consistent data:
You must program FB 192 in the IM 308C to enable the transfer of consistent
data between the DP master and the I slave. The effect of FB 192 is that the data
of the IM 1517 CPU is only output or read out continuously in a single block.